Raw Water Storage Tank:
Automatically controls water intake; the inlet valve (pneumatic butterfly valve, oversized to accommodate low municipal water flow velocity) closes when the tank is full, effectively preventing water hammer.
Plate Heat Exchanger:
Provides pasteurization for the pretreatment system while regulating raw water temperature (automatically controlled via setpoint).
Sterilization timing starts automatically once the return water temperature meets requirements.
Equipped with a bypass control valve to maintain operation during heat exchanger maintenance/cleaning.
Raw Water Flow Monitoring:
Online flow meter for real-time inflow measurement, with a manual diaphragm valve for fine flow adjustment.
Multi-Media Filter (MMF):
Constructed in 304 stainless steel with vulcanized rubber lining.
Utilizes butterfly valves for high-flow inlet control.
MMF Pressure Monitoring:
Inlet/outlet pressure gauges for backwash/forward wash triggering based on differential pressure.
MMF Drainage & Sampling:
Bottom drain valve and dedicated sampling port.
Activated Carbon Filter (ACF):
304 stainless steel with vulcanized rubber lining; butterfly valves for high-flow intake.
Shell-type activated carbon for enhanced chlorine removal.
Online outlet temperature monitoring to optimize sterilization efficacy.
ACF Drainage & Sampling:
Bottom drain valve and dedicated sampling port.